    摘要:

    V国X电厂循环水泵房的大型深基坑发生过坍塌事故,为了查找原因,分别采用等值梁法和m法计算了支护结构的受力状态。介绍这两种方法的计算原理,并以该工程为实例进行计算,两种方法计算的结果均显示支护桩最大应力均超过了钢材的允许应力,这正是坍塌事故发生的必然原因。

    Abstract:

    A collapse accident occurred in large deep foundation pit of X power plant circulating water pump house in V country.To find the reasons,we use the calculation method of “equivalent beam” and“m” to calculate the force state of the supporting structure.The calculation principle of the two methods is described. Based on this project,we carry out the calculation.The results show that the maximum stresses of the supporting piles are more than the allowable stresses of the steels,which is the inevitable reason of the collapse accident.

    参考文献
    相似文献
    引证文献
引用本文

唐蔚东,吴姚平.大型深基坑支护结构的理论计算与分析[J].水运工程,2016(5):141-145.